Raise your Query

Hi! Simply click below and type your query.

Our experts will reply you very soon.

WhatsApp Us

Standard of Copper Fittings


ANSI B16.22 for refrigeration and HVAC

O.D. (in)O.D. (mm)
I.D. (C)
O.D. (FTG)
Length (C) (M1)Length (FTG) (M2)Min. Thickness (T)
MaxMinMaxMin
1/86.356.506.406.376.308.09.00.56
/7.948.108.007.987.908.09.50.61
1/49.529.689.589.559.478.09.00.66
3/812.7012.8512.7512.7212.629.510.00.79
1/215.8816.0315.9315.9015.8012.512.00.91
5/819.0519.2019.1019.0718.9716.016.00.97
3/422.2222.3822.2822.2522.1419.018.01.04
/25.4025.5625.4625.4325.3517.018.51.10
128.5828.7528.6528.6228.5023.022.01.17
31.7531.9131.8131.7831.6521.022.51.20
1 1/434.9235.1035.0034.9734.7024.525.01.27
/38.1038.3238.1738.1438.0025.026.51.30
1 1/241.2814.4841.3541.3241.1728.028.01.40
/50.8051.0250.8850.8450.7031.032.51.60
253.9854.1854.0554.0253.8734.034.01.63
2 1/266.6866.8866.7566.7266.5737.538.01.88
/76.2076.6576.3076.2876.1038.039.52.00
379.3879.5879.4279.4279.2742.043.02.11
3 1/292.0892.2892.1292.1291.9748.549.02.36
4104.78104.98104.82104.82104.6755.055.02.57

EN1254-1 & BS864-2 FOR MEDICAL GAS PIPE LINE AND PLUMBING

O.D.
I.D. (C)
O.D. (FTG)
Length (C) (M1)Length (FTG) (M2)Min. Thickness (T)
MaxMinMaxMin
8.08.158.068.047.956.88.80.6
10.010.1510.0610.049.957.89.80.6
12.012.1512.0612.0411.958.610.60.6
14.014.1514.0614.0413.9510.612.60.6
15.015.1515.0615.0414.9510.612.60.7
16.016.1516.0616.0415.9510.612.60.7
18.018.1518.0618.0417.9512.614.60.8
22.022.1822.0722.0521.9415.417.40.9
28.028.1828.0728.0527.9418.420.40.9
35.035.2335.0935.0634.9323.025.01.0
42.042.2342.0942.0641.9327.029.01.1
54.054.2354.0954.0653.9327.029.01.2
64.064.3364.1064.0763.9232.034.01.4
67.067.3367.1067.0766.9232.034.01.4
76.176.4376.2076.1776.0235.536.51.6
88.989.2389.0088.9788.8237.540.51.8
108.0108.33108.10108.07107.9247.551.52.1
159.0159.53159.20159.10158.9070.075.02.5